logo

Calculating Heat Loss

Our interest in heat loss is in sizing our HVAC equipment, sizing windows for solar gain, determining insulation levels and the size of PV system needed to achieve zero energy, and of course simply estimating what a building's yearly energy cost will be.

Modeling energy use is theoretically simple, but practically complex, particularly over longer time periods.  Occupant behavior such as thermostat setting, opening windows, and equipment use have a very large effect on building energy use.  Likewise, energy use literally changes with the weather. On top of all this, add in radiant heat/loss gain (see discussion in the R-values section), and that fact that real-world assembly R-values vary somewhat from theoretical ones (see next section).

There are numerous software packages that calculate heat loss (including some free ones), some of which can do some very sophisticated modeling in an attempt to deal with the practical complications.   Different programs have different capabilities, so the best one depends on what you want out of it.  Even if you do buy a package, keep in mind that annual energy use is so dependent on occupant behavior and weather, no model can possibly predict the end result accurately.5  The more sophisticated packages will take more effects into account and hence get a better estimate, but you can still get useful estimates with just a simple model done in a spreadsheet.

 If the concern is only ballpark yearly energy use, or only worst case energy use (for example to size a backup heating system), or typical case energy use, a simple spreadsheet will give a good result.  The rest of the document describes how to do this, and explains the limitations of this approach.

Heat Loss = Conduction + infiltration

There are two primary methods of heat loss in building, conduction thru the building envelope (ie the exterior surface: floor, walls, roof, windows, etc) and via air infiltration (or rather warm air escaping the building being replaced by cold outside air). Other factors, such as radiant loss/gain really only affect the temperature difference from inside to out. Those factors can be quite significant for short periods of time, and may even significantly affect the yearly amount, but are ignored here.6

Heat loss thru the envelope

The general heat loss formula is: Q=U*A*ΔT, or in plain words, the heat loss of an area of size A is determined by the U value of the materials and the difference in temperature between inside and out (that is the difference in temperature of the two surfaces, not the two air temperatures, which might not be quite the same.  Below is an adjustment for air temperatures.)

To get the heat loss of an entire building, you divide the building into areas that have the same U value, and then add them all up to get the total heat loss.  So typically you will end up with four different areas: walls, windows & doors, roof and floor.  If one of those areas had parts that have a different U value (for example a wall bump out that is constructed differently), you will end up breaking that into its own category also.

Heat loss thru an assembly:
Because walls, roofs etc are assemblies of different materials, calculating heat loss thru that assembly requires combining the R-values of the various materials to calculate an effective R-value for the assembly.

First, divide the assembly into sections that are uniform from inside to outside, for example in a 2x4 wall, there is the part where insulation fills the cavity and the part where there is a 2x4 and no insulation.

Second, calculate the R-value of each section by adding of the R-values of each of its layers.  For example, a typical 2x4 wall would be: R.5(wood siding)+R.5(plywood)+R11(insulation)+R.5(sheetrock)=R12.5.  The R value of a material is either found in a table for the entire material(eg an R11 fiberglass batt which is 3.5" thick), or by using the R value per inch of material (eg R3.1/inch) and multiplying by the actual thickness (R3.1/inch*3.5inches=R11).

Third, calculate the U value of the assembly as the sum of the weighted U values of each section.  To do this, you will first need to calculate what percentage of the total area each of the different sections occupy.

Uassembly = U1*%area1+U2*%area2+...

The R value of the assembly is then just the inverse of its U-value.

Here is an example:

wall sectionThe example wall section at right consists of  two different cross sections: (A) where there are no 2x4 studs: it's sheetrock-insulation-plywood-siding, and (B) the section where there are studs: it's sheetrock-2x4-insulation-2x4-plywood-siding.  In this example, the 2x4s are 24" apart, that means every 24" section of wall consists of 22.5" of assembly A and 1.5" of assembly B.

The R value for section A is: .6 (sheetrock@ R1 per inch) + 33.3 (cellulose@ R3.7 per inch) + .5 (plywood@ R1 per inch) + .5 (siding+air barrier: estimate )=34.9.  The R value for section B is .6 ( sheetrock) +3.5(2x4)+7.4 (cellulose) + 3.5(2x4) + .5 (plywood) + .5 (siding) = 16.

To get the R value of the complete wall, we add up the U values of each section multiplied by what percentage of the overall assembly they represent, and then take the inverse.  For our sample wall, section A is 94% (ie 22.5" out of 24"), and so section B is 6%.  The basic formula is:  Uwall = Ua*Pa + Ub+Pb + Uc*Pc +
 .... where Ux is the U value of a section and Px is the section's percentage of the whole.
For our wall, Uwall = (1/34.9)*.94+(1/16)*.06 = .0307, which is a R value of about 32.5.

In a actual wall there are significant differences from this simple wall section, for example there are often double or triple studs in the corners, there are top and bottom plates, headers of various sizes on windows, fire blocking, electrical outlets, plumbing, vents etc.  An accurate value would require breaking the wall up into each different component section, while a good ballpark would be to double (or maybe 1.5x) the effective size of the lesser insulated area.  In any case the effect isn't that large:
Doubling the less insulated area is (1/34.9)*.88+(1/16)*.12=R30.6
while increasing it by 1.5 times is  (1/34.9)*.91+(1/16)*.9=R31.5

There are two complexities here: (1) that conditions the wall is under are different from the assumptions behind this equation (mostly due to the radiant temperature being different than the air temperature, see R-values for the full discussion) and (2) that the insulation material itself maybe degraded are installed improperly.  Both can be big factors, and less-than-perfect installation is probably more than norm than a rarity.  Batt insulation is notoriously hard to install so it fills the cavity evenly.  Blown in loose fill is easier, but still not trivial, and if not installed dense enough, it will settle and leave voids at the top of walls.  In this case, the final R-value depends on the fill being installed to the specified density.  With loose fill, the R-value increases with increasing density up to a point, but goes down after that.  It is generally quite difficult to pass that point, at is requires compressing the insulation.

Left out of this calculation is the effect of the air layers on the inside and outside of the assembly (for a more detailed explanation see "Air Layers").  Typical values are R.7 for the inside layer, and R.2 for the outside.  These are averages, with built in assumptions about the conditions the wall experiences.  Note that ceiling/roof values are somewhat lower.  Because they are relatively small compared to super-insulated assemblies, and because real-world assemblies tend to have more structural material, more pipes, more wires, and less-than-perfect installations of insulation, the air-layer R-value is ignored throughout the sensiblehouse documents.

Heat loss thru a slab, basement wall or crawl space:
Calculating the heat loss thru a slab involves two additional difficulties; first that soil has a high specific heat and second that the R value of different soils varies considerably.  Further complicating the issue is that the ground under the middle of a slab stays at a nearly constant temperature all year, while the ground near the edge changes with the weather (albeit, somewhat slower than daily temperature changes).

To get around this problem, engineers have calculated approximations for the heat loss thru an entire slab, which is given as a factor F, which is a heat loss amount per linear foot of the perimeter of a slab (whereas R and U are per square foot).  So for a slab or basement, rather than calculating the surface area and multiplying by the U value, you calculate the length of the perimeter and multiply by F. These values are given in tables which depend on specific construction (walls versus slab), and amount of insulation (an example, from Seattle's energy code website, for slabs is here.)

Because heat loss thru the perimeter is assumed to dominate the heat loss thru a slab, builders have traditionally only installed insulation under the perimeter of a slab, with a 2-4' width around the perimeter being typical.  Green builders have begun to question whether this is sufficient, especially when the slab is heated, or is a solar thermal mass slab, and it is now more common to put insulation under the entire slab, typically 2".  Because insulation also raises the temperature of the slab, extra slab insulation will also increase the room's mean radiant temperature. In the future, it is likely that not only will full slab insulation become standard, but much thicker amounts seem likely also.

(The following is speculation) By insulating to a high level (potentially including significant vertical insulation to prevent perimeter losses), it is possible to get a better estimate of heat loss without using F values.  Since virtually no one currently does this, you won't find F values for the situation in tables. Calculate downward losses, using the difference in temperature between inside and average ground temperature.  Calculate perimeter losses by assuming an average depth to which the losses occur, and use the temperature difference between inside and outdoors.

Finally, here is a quick summary of why calculating heat loss thru a slab is difficult...

The R value of soil is determined by how dense it is (sand versus clay), but more importantly by how much water is in it.  Dry sand might be R2 per foot, depending on how dense it is, while dry clay is likely similar to concrete (about R1 per foot), while wet clay might have almost no R-value at all.  Because soil is often not homogenous, and its moisture content changes, you are stuck using either worst case, or a guesstimate average.

Because soil can store a significant quantity of heat (assuming it is either dry, or its water content isn't moving, both of which can be bad assumptions in some climates), the area under a slab or basement will tend to warm up, forming a bubble of heated soil under the house that is warmest near the slab, and cools further away.  The size of the heat bubble affects the effective width of the soil that adds to the insulating value of the slab. It is common practice to assume the heat loss directly down is negligible, and instead calculate loss only thru the edge.

Crawl spaces:
While the ideal crawl space is ventilated so that its at outside temperature, in reality this never happens.  As a result the heat loss to a crawl space is less than to the outside.  Energy codes will typically have an adjustment factor that you are required to use, or you can estimate by just increasing the effective R value by some amount.

(Aside: since humidity problems come along with this reduced heat loss, some people recommend that crawl spaces be part of the conditioned space (ie heated), although it seems like in that case, you'd be better just not building them at all, or leaving the underside completely open, as in a home on poles.  Another alternative is a fully conditioned basement.)

Heat Loss via Infiltration

In addition to heat loss thru the envelope via conduction, all buildings leak air.  This leakage comes thru places like fan vents, seals around windows and doors, and leaks thru small cracks in the walls, ceiling and floor.  The amount of leakage is dependent on the difference in pressure between outside and inside, which is due to three factors:

  • Wind: wind raises the pressure on the windward side of the house, and lowers the pressure on the leeward side, resulting in air being both pushed and pulled thru the building.
  • Stack effect: when the outdoor air is cooler than the indoor air, the indoor air wants to rise thru the ceiling via convective pressure.  The greater the temperature difference, and the taller the building, the greater the pressure.  Stack effect is generally smaller than the effect of wind.
  • Imbalanced mechanical ventilation: dryer vents, range hoods, and especially downdraft cook tops force air outside without bringing any back in, resulting in lower pressure inside than outside, which in turn, sucks air in from outside.

Because the conditions that cause infiltration vary significantly, infiltration is measured a specific pressure difference via a device called a Blower Door.  With this device placed in an exterior doorway, the house is depressurized to be 50 Pascals less than outside (which is the equivalent of a steady 20mph wind blowing at all sides of the building).  Once this pressure is achieved, the devices measures the airflow it needed to produce this pressure, which of course is the same as the airflow leaking into the house thru all of its various cracks.

This measured value can then be converted to an average amount over the course of the year by using a statistical technique that takes into account local weather, site exposure and building height, so for example buildings in windier climates will have higher numbers.  While the technique is beyond the scope of this document, its result is simple: you look up a fudge factor for your location and building height in a table, and divide the blower door result by that number.  If you don't have the table, you can just divide by some number1 between 20 (not very windy climate) and 10 (windy climate) and get a decent estimate--no real need for accuracy here since the number is an estimate anyhow of weather averaged over many years.   See this in Home Energy magazine for background on this conversion. 

Note on nomenclature: the term CFM50 refers to the air leakage number in cubic feet per minute as measured at 50 pascals.   The ACH50 number is just the CFM50 number converted to a ratio based on the volume of the house.  So when you see 3ACH50, that means that the building has 3 air changes per hour at 50 pascals; likewise when you see 100CFM50 it means that the building leaks 100CFM at 50 pascals.

Occasionally air leakage is measured at a pressure of other than 50 pascals, and so if the pressure used was 30 pascals instead, the values would be written as CFM30 and ACH30. You will rarely see any number besides CFM50 mentioned. 

When these numbers are converted to the average, the value is referred to as the natural ventilation, and usually designated by ACHnat or CFMnat

In addition to CFM and ACH, leakage is also sometimes described by an equivalent leakage area, which is the effective size of the hole.  While useful for visualization, it is not used in calculations.

Leakage is also sometimes specified as equivalent leakage area, which is the effective size of all the leaks in the building. While useful for visualization, its not generally used in calculations.

The CFM50 number is typically also converted to ACH50, which is the equivalent number of air changes per hour based on the volume of the house (eg a 10000ft3 house that leaks 100CFM50, would be .6ACH50--note that you need to convert CFM to cubic feet per hour.  If Vh is the volume of house, then ACH50=CFM50*60/Vh.  Since larger buildings have more surface area to leak from, ACH50 is a good way to compare the relative tightness of two buildings since its a value that is essentially the percentage of the air in a building that leaks out in one hour.  A building that is less than 1ACH50 is considered extremely tight, one that is less than 2ACH50 is tight, one that is less than 3ACH50 is moderately tight, 3-5ACH50 would be typical, and anything more than 5ACH50 is leaky.   Its not that unusual for older building to be 10ACH502, or even to be so leaky that the blower door can't pump enough air to reach 50 pascals. Of course what is tight, very tight etc is pretty subjective, and not everyone will agree on the classification here.

While ACH50 is useful for comparing the relative tightness of building, the original CFM50 number tells the absolute leakage, and hence the absolute energy use.  A 3000SF building measuring 2ACH50 will take more energy to heat than a 1000SF building also at 2ACH50--even if the 3000SF building were 1ACH50, it would still lose more heat than the 1000SF at 2ACH50.

Once you've converted the CFM50 rate to a "natural" flow rate that represents typically heating season, you can now calculate the heat loss due to infiltration.  To do so, you use the heat capacity of air (which is .018 BTU/ft3-°F), times volume, V that leaks out in an hour.  This volume, V, is the total volume of the house times the ACH number (or alternatively use the CFMnat  times 60 to get cubic feet per hour) of air movement, times the difference in temperature:  Q=.018*V*ΔT.  This is because the heat loss is all due to how much heat is contained (and carried off) by the air leakage; or alternatively its how much heat is necessary to heat the outside air that has replaced the warm air that leaked out.

For more information on infiltration and ventilation see the ventilation section.

Heat Loss Calculation Example

The following is an example house, to show a complete heat loss calculation. This house is 25'x40' (1000SF) on the interior with an 8' ceiling, is built with the double stud wall shown in the example above, double glaze low-E windows (U .3), R5 doors, and has a unheated crawlspace.  To simplify things, rather than using F values for floor loss, it is assumed an un-vented crawlspace has an average temperature of around 55°F3.  Assume the floor and the ceiling are built with 12" TGIs (or equivalent), and that the insulation is blown in cellulose (R3.7/inch - or equivalent).The following are the east, south, west and north elevations for this hypothetical house (which is simplified to make the calculations easy: its intended to be realistic enough, but it isn't a real house).  Assume that the house measured 2ACH50, which corresponds to a .2ACH  natural ventilation rate (which in turn is about 27CFM).  Because this is quite small, assume another 25CFM mechanical ventilation.

For this example, we assume the house is in a moderate climate, with an average heating season temperate of around 40°F, and typical coldest night is around 20°F.  The heat loss at typical temperature will help calculate an approximation of what percentage of the necessary heat can be supplied with passive solar, while the heat loss at the coldest day will help size the backup heating equipment.   Local codes specify this typical cold temperature, usually called the design temperature, which for Seattle is 23°F.

example  house
Assembly Area U BTU/F ΔTtyp BTU ΔTcold BTU
Windows 141 .3 42.3 30 1269 50 2115
Doors 40 .2 8 30 240 50 400
Walls 859 .03 26 30 780 50 1300
Floor 1000 .02 21 15 315 15 315
Ceiling 1000 .02 21 30 630 50 1050
Conduction Total     118.3   3234   5180
  Volume ACHnat BTU/F        
Infiltration 8000 .2 28.8 30 864 50 1440
Ventilation   .1875 27 30 810 50 1350
Totals     174.1   4098   7970

All of the Btu values are per hour.  To get a daily amount, use the average daily temperature to get an hourly loss, then multiply by 24. Because this house is super-insulated, and quite small, these values for heat loss are very low compared to typical heating systems, whose maximum output is more in the 40,000 to 80,000 Btu/hr range.  For a more fair comparison, we should size the heat for the most extreme cold day, say 0°F, but even then this house still uses only 10,000 Btu/hr.

Yearly heat loss/Accuracy of the model

The heat loss model described here is for steady state heat loss under ideal conditions.  In the real world, these conditions are at least as uncommon as they are common (detailed discussion in the section on r-values).  How much the actual loss will vary from the modeled loss is unclear.  There are really only two significant factors: the sunny surfaces of the building will likely have a lower heat loss due to radiant gain, and roof heat loss will be higher when the night sky is clear and dry. Under a cloudy sky at night, the model should be pretty accurate, and on a cloudy day it will also be relatively close (although there will still be some radiant effect), but at all other times real loss will vary from the model.

While the heat transfer on a given day isn't likely to be much different from what is calculated, a small error in the daily amount will result in a significant error in the  yearly amount.  In addition any given years weather will vary from the average, so the annual heat loss calculation should be viewed as a ballpark estimate. Finally nightime setback (or for that matter any setback) in the thermostat setting may change your  heat loss. Still, the yearly heat loss calculation can be used to compare one building to another fairly accurately, and will still provide a decent estimate of annual energy use (although you will have to factor in internal gain and solar gain, see the passive solar section).

To estimate the yearly heating and cooling energy, you calculate the building's heat loss per degree (ie just Q=A*U), multiply by 24 to convert hourly loss to daily, then multiply by the number of degree day for your location (for a discussion on degree days and its limitations, see the units section).  So, for example if the example house from above is located in a 4000HDD climate, its seasonal loss will 174.1*24*4000, or about 16.7millon BTU.  The cooling energy is calculated the same only using the CDD number instead.

 The other catch is that if that buildings are usually kept at 68 to 70F, not 65F, so the actual heat loss is likely more than 16.7million BTU.  HHD numbers for indoor temperatures other than 65F are available, but my experiments indicates they give too large a result--at least for Seattle--and I'm assuming its because almost every day in Seattle has an average temperature below 70F, yet clearly many of them are close enough to 70 (and with enough sunshine) that no external energy is used--yet you can't weight the solar gain against the heat loss because its likely to be greater than the heat loss, and the windows are likely to be open to exhaust all the extra gain.4

Note also that real world buildings are much more complex than the simple model presented in the above example: the R value of a wall varies by how much lumber is actually in it; some wall sections often end up getting built differently than others; pipes, ducts and other voids reduce R-value to less than the nominal value; and most buildings have quite a few more than four wall surfaces.  The more accurately all these things are accounted for, the more accurate the result will be.


Notes

1. Like everything else in heat loss calculation, this is an educated ballpark.  It has never been clear to me whether the standard adjustment is really valid for the heating season, or includes too much of the non-heating season.  What is clear, is that on the coldest days, the infiltration is going to be more than the adjusted ACH50 value.

2. this is based on a conversation with a energy retrofit specialist, who said he regularly found houses with 3ACHnat which depending on what conversion was used, corresponds to an ACH50 of between 30 and 60.

3: a vented crawlspace will presumably have a lower temperature during the heating season.  There are more complex methods of calculating this downward loss, but because we are only interested in a ballpark result, this simplification is probably reasonable.

As an example of using F-factors, if instead we assumed the house was slab on grade with full R10 insulation, we would find the F factor from the table of .36 is the slab is unheated and .55 if it is heated.  Since the perimeter of the house is 130ft, this gives a loss/°F of between 46.8Btu & 71.5Btu.  Since these values are higher than the one in the table, it suggests a higher level of slab insulation is probably in order (and/or vertical perimeter insulation),but unfortunately Seattle's tables doesn't have F values for more highly insulated slabs.

4. I've spent a bunch of time trying to make my model of the Seattle house match the energy use I actually see--unfortunately we have a gas stove, a gas dryer and gas hot water, so there is extra work in separating those out from heating energy.  Using HDD (65F), I get a loss of 45mBTU/yr, which is the actual, but I also calculate that I have 10mBTU of internal gain (electrical load) and anywhere from 7-12mBTU of solar gain.  When I tried HDD (70) I got a loss of more like 60mBTU, which is too high...but then the house is typically at 68F

Either there is a sizeable error in my model, or HDD just doesn't give a good result.   While my model does likely have errors, I'm convinced HDD doesn't give that good a result.  See this article http://www.energylens.com/articles/degree-days for a detailed discussion.  In particular HDD (65F) underestimated because the building is typically warmer, and any other HDD values are too large because the model assumptions are wrong when the temperature is over 60F outside--the heat is usually off, and an excess night heat loss just results in indoor temperatures going below 68F, then climbing back to it or above during the day.

5: In particular, when upgrading to super-insulation, there is some tendency to keep a house warmer than it would have previously been, so the net savings is sometimes smaller than expected.

6: No source I could find dealt with these factors at all, nor could I find any data to indicate how big they are.  The typical response is to just put more insulation in the attic for instance, because the summer roof is often hotter than air temp, and the winter roof is often colder.