|
We have seen that even in a very leaky house it is easy to
find weather conditions that result in no pressure difference from inside to
out, and hence little to no incoming fresh air: in fact this will
occur any time there is little wind and the outside and inside temperature
are similar. We have also seen that the amount of air coming into a
leaky house varies dramatically with weather, and that too much air leaks in
during the extreme weather conditions (see energy
section). The demand for fresh air, on the other hand, has
to do with the number of occupants and is fairly consistent all year
long. Each person needs not only fresh air to breath, but needs
pollutants and excess water vapor removed.
Fresh Air Requirements
The most commonly agreed on standard fresh air requirement is that 1/3 of
the volume of air in the house should be replaced with fresh air every hour
(stated as 1/3 ACH or .35ACH, with a little rounding). Because this amount
will vary with the volume of the house, an alternative statement is that
each person needs 15CFM. The difference between the two is
significant: two people getting 15CFM results in 1800 cu ft per hour, which
is only 1/10 of the volume of a 2000 sq ft house, or about 13% of a 1500 sq
ft house. In practice the amount of fresh air necessary will also
likely vary significantly based on how many pollutants are likely to be
introduced into the house, and how much spot ventilation will work to
control them. A home where shoes are left at the door, without
pets, without hobbies that involve toxics, without toxics cleaners and
pesticides and that avoids VOCs, will need much less fresh air than ones
which do have some of these things.
All houses will have some natural ventilation, and that
amount will be greatest when the wind is high and the temperature outside is
cold. This component of ventilation is usually ignored because it is
not reliable, but may be great enough during the winter such that mechanical
ventilation is either not needed or the need is much reduced. The
problem with this approach is the question of whether accumulated pollution
and excess moisture is removed by natural ventilation, and in the case of
moisture, whether it collects in walls or other undesirable places on the
way out. The topic of mechanical ventilation is a source of much
controversy, and will probably continue to be so for a while.
Where ventilation is needed
Some fresh air is needed everywhere, but pollutants and excess moisture are
usually confined to specific areas. As a rule of thumb, fresh air is
generally supplied to rooms that are most frequently occupied (bedrooms,
living rooms) and exhausted from rooms that generate the most pollution
(kitchens, bathrooms, offices).
-
Kitchens - cooking can create both excess moisture and
odors, and so a range hood that vents to outside is normally used to
eliminate these sources. Circulating fans (ie no duct to outside) are not
effective at all. Any ventilation in the kitchen needs to have a grease
filter in it to avoid gumming up the ducts and fan. Downdraft cooktops
work by sucking large quantities of air (to fight capture the warm waste air
from cooking, which wants to rise), and because of that can remove all the
air in a house in short order. A 600CFM downdraft fan will remove all
the air in a 2000 sq ft house in about 30 minutes. It is not advisable
to use these, but if it is used a window should be opened, or other source
of make-up air used to prevent the house from de-pressurizing. Since
there are no sealed combustion gas ranges available yet, the use of a gas
range will consume oxygen and produce carbon monoxide and polyaromatic
hydrocarbons.
-
Bathrooms - bathing produces significant excess moisture
which generally requires 30-60 minutes of a fan running at 50CFM to remove
it. Because this amount of fresh air is much greater than the amount of
fresh air normally needed a separate exhaust fan should be installed and
connected to a crank timer which allows the fan to automatically turn off
when it is done.
-
Laundry - dryers produce excess moisture and should be
vented to outside. Since most people hang some clothes to dry, a spot
exhaust fan should be installed.
-
Utility - Furnaces and hot water heaters should be sealed
combustion units, which are self venting to outside.
Understanding Air Flow and Air Pressure
Air moves from areas of high pressure to low pressure until the pressure
difference is zero, unless there is a barrier to prevent it. Like water, air
will go through all susceptible openings, and almost all barriers will fail
to prevent it doing so. Air pressure differences are created due to a
natural conditions or by mechanical fans. Areas in a house are often
at different pressures, and the house can be at higher pressure than outside
or lower. Although these pressure difference can be undesirable, we do
our best to prevent them and live with the rest.
There are two natural driving forces for natural air
movement: temperature and wind. Everyone has hear the old adage that
heat rises, but in fact heat moves from warm to cold in all directions
equally. What does rise is warm air, because it is lighter than cold
air. This principle has been used in hot climates to provide natural
cooling, but on cold days it causes increased pressure on whatever barriers
exist near the top of the house. It also tends to cause the upper
floors of a house to be warmer than lower ones. Wind causes areas of
higher pressure on the side of the house it strikes and lower pressure on
the other side, putting pressure on windows, doors and wall to let it
through. Wind moving over the top of a chimney creates a suction which
pulls air out of the house.
One special case of natural ventilation is due to fireplaces
and some wood stoves: these devices not only consume oxygen, but the
hot air that rises up the flue sucks the warm out of the house and out the
chimney. This is a case where an extreme temperature difference
creates a very large air flow.
(pictures of air movement!)
Types of Ventilation Systems
There are three types of mechanical ventilation systems, and a strategy for
passive natural ventilation. No matter how a house is built it is
likely to have some degree of natural ventilation and during some of the
year, that amount may be sufficient to meet the house's fresh air
needs. Mechanical ventilation has the advantage of easily removing
contaminated air in addition to supplying fresh air, in addition to be able
to provide filtration by circulating the air in the house.
Exhaust Only Ventilation
In the simplest form of this system a spot ventilation fan (typically the
bathroom) is fitted with a timer that turns the fan on for part of the day
every day. This system forces air out of the house, de-pressurizing it
so that outside air will leak in to return the pressure to zero. If
the house is sealed very tight, one or more vents are installed in the
window or wall (typically in the bedroom) to allow makeup air to
enter. In the more complex version, a whole house fan is used with a
duct system to remove air from multiple locations (bathroom, kitchen, office
an closets are typical). There are two disadvantages of this system:
first is that if the pressure gets too low, backdrafting can occur (that is
the exhaust from a furnace, hot water heater, etc will go in the house
instead of us the chimney). The second problem occurs when a basement
or crawlspace has a higher pressure than the rest of the house, any radon or
mold down there will then be drawn up into the house. The degree that
this is a problem depends somewhat on how tight the house is, as ventilation
systems usually ran at fairly low volumes: 50-100 CFM, and so the pressure
difference they create is often quite small. In both exhaust and
supply ventilation systems, the heat lost due to the air that leaves the
building must be made up by the heating system.
Current Washington State code requires the simple exhaust
ventilation system as the minimum ventilation requirement, but many people
disable them.
Supply Only Ventilation
This system is the opposite of exhaust only: rather than pumping air out of
the house, air is pumped in. While this prevents backdrafting and
drawing pollutants from a crawl space, positive pressure in a house
increases the driving force of water vapor to move through walls, increasing
the chance of excess moisture collecting in walls. As with the exhaust
only system, vents can be added to give the air a way out, but depending on
weather they can also work backwards.
Balanced Ventilation
This is the system of choice as it (hopefully) has no effect on the air
pressure in the house. Its biggest drawback is that it has a higher
initial installation cost. In this system, air is pulled out of some
rooms and put into others, with ducts distributed fairly evenly throughout
the house so that the overall air pressure is balanced. The most
common kind of balanced ventilation is the Heat Recovery Ventilator (HRV),
because it captures much of the heat from the exhaust air and uses it to
heat the incoming air, resulting in very little energy penalty.
Balanced ventilation systems often share the same ductwork as a forced air
furnace.
Duct layout
Whether or not ducts are used for delivering heat, they should be kept
inside the building's envelope to prevent heat loss. They also should
be sealed tightly (mastic works best, duct tape often fails) to prevent dust
from wall cavities from entering them, and so no wall cavity should be used
as a duct without a metal liner. Smooth metal ducts are preferred
since they provide the least resistance to air flow, and so reduce the
strain on the heating and ventilation system fan motors. It is also
important to size the ducts to allow for sufficient air flow as well as to
avoid bends, especially sharp bends, whenever possible as they also increase
the back pressure making the motors work harder.
In a forced air system the ducts are designed to deliver
enough heat to each room, while in a ventilation system they have to deliver
enough fresh air. The air movement requirement for heat delivery is
much greater than that for ventilation (5-10 times greater), so any duct
system capable of delivering heat will deliver fresh air effectively.
In forced air systems, there is usually only one or two air returns, which
if placed so that warm air is delivered evenly, will also deliver fresh air
evenly. The disadvantage of having limited returns is that closets and
offices may not be ventilated enough.
In ventilation only systems, air is supplied to the rooms
that are most occupied and removed from ones that cause the most
contamination. While this sounds good in theory, the two largest
sources of water vapor (kitchens and bathrooms) will not be well served by a
whole house ventilation system because they need a much higher volume of
air, and so those locations will need spot ventilation fans anyhow.
Closets and offices could be well served by a whole house system.
Getting the right amount of air in each room is accomplished
by installing dampers on the path to each duct and adjusting them so that
the right amount of air comes out.
Filtration (types & efficiency rating)
The filter that is normally installed in furnaces is only good at keeping
very large particles out of the furnace (to protect it), and does little to
stop dust, and nothing to stop the fine duct particles that are of health
concern. There are unfortunately a number of different rating systems
used for filters so when you buy a filter that is "90% efficient"
you need to know what it is 90% efficient at removing, as they are rated by
one of three methods: the arrestance method, the dustspot method and the
D.O.P method. A filter which is 97% efficient in the
arrestance method, is only 50% efficient in the dust spot method, and only
10% efficient by the D.O.P. method. Medium efficiency filters are
rated by the dustspot method, and a filter of 30-40% should be the minimum
standard, with a 60-70% filter being a better compromise. HEPA filters
are the cream of the crop, typically achieving 95% efficiency in the D.O.P.
method.
As the efficiency of a filter goes up, so does it resistance
to air flow, and so the efficiency of the filter is usually limited by how
much it affects the furnace or ventilation fan. One way to get higher
efficiency without affecting the blower motor is to increase the diameter of
the filter, which increases its surface area.
References
Understanding Ventilation, John Bower, Healthy House
Institute, 1997
Builders Guide Series, Joe Lstiburek, EEBA, 2000.
The Health House Workbook, American Lung Association,
1995
Healthy by Design, David Rousseau & James Wasley,
Hartley & Marks, 1997
|